GN1200 Fire Resistance Wire 350℃~1200℃

Fixed laying, plus flame burning, no harmful toxic gases. This product is metallurgical, thermal, petroleum, chemical, natural gas, kerosene and other special circumstances, the need for fire performance of the various electrical devices used in the wire and cable.


Product Detail

FAQ

Product Tags

GN1200

Video display

Product Model: GN1200
Implementation criteria: Q31/0114000683C001-2017
Product Features:
1, rated voltage: 300 / 500V
2, the working temperature: 1200 ℃
3, conductor: stranded pure nickel wire
4, insulation: high temperature yarn + glass fiber woven + fluoride mica tape
5, color: white

Features / Uses: Fixed laying, plus flame burning, no harmful toxic gases. This product is metallurgical, thermal, petroleum, chemical, natural gas, kerosene and other special circumstances, the need for fire performance of the various electrical devices used in the wire and cable. Delivery requirements: According to the agreement agreement agreed to allow not less than 10 meters of short delivery. The quantity shall not exceed 10% of the total length of the delivery. Specification structure and technical parameters:

标称截面 mm2

Nominal cross section (mm2)

导体 ( 支数 / 线径 ( Φ mm) Conductor structure Root number / diameter (mm)

绝缘平均厚度

Insulation thickness (mm)

电线外径 mm

Outside diameter control (mm)

20℃时导体电阻最大值Ω/KM

20 ℃ conductor DC resistance (Ω/km)

 

包装 ( / )

 Packing length (m)

 

0.5

7/0.30

0.5

2.0±0.3

160.4

200

0.75

11/0.30

0.5

2.2±0.3

106.8

200

1.0

14/0.30

0.5

2.4±0.3 

80

200

1.5

21/0.30

0.5

2.6±0.3

54.8

100

2.0

28/0.30

0.5

2.8±0.3

42

100

2.5

35/0.30

0.5

3.1±0.3 

32.8

100

4.0

56/0.30

0.6

4.0±0.5

20.4

100

6.0

84/0.30

0.6

4.8±0.5

13.6

100

10.0

140/0.30

0.6

5.8±0.5 

7.8

100

16

228/0.30              

0.6

7.0±0.5

4.96

100

25

361/0.30

0.6

8.8±0.5

3.18

100

35

494/0.30

0.6

10.0±0.5

2.26

100


  • Previous:
  • Next:

  • Write your message here and send it to us